VEGA VEGABAR 86 Save sensor - Operating Instructions User Manual
Page 30
30
6 Set up with the display and adjustment module
VEGABAR 86 • Slave sensor for electronic differential pressure
45052-EN-131011
Note:
If the adjustment ranges are exceeded, the entered value will not be
accepted. Editing can be interrupted with [ESC] or corrected to a
value within the adjustment ranges.
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Adjustment", then "Min.
adjustment" and confirm with [OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value (e.g. 10 %) with [+] and save
with [OK]. The cursor jumps now to the pressure value.
4. Enter the pressure value corresponding to the min. level (e.g.
0 mbar).
5. Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
The min. adjustment is finished.
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
Proceed as follows:
1. Select with [->] the menu item "Max. adjustment" and confirm
with [OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value (e.g. 90 %) with [+] and save
with [OK]. The cursor jumps now to the pressure value.
4. Enter the pressure value for the full vessel (e.g. 900 mbar) cor-
responding to the percentage value.
5. Save settings with [OK]
The max. adjustment is finished.
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Min. adjustment" and confirm
with [OK].
Setup - Min. adjustment
Level
Setup - Max. adjustment
Level
Setup - Min. adjustment,
flow