6 Set up with the display and adjustment module

VEGABAR 86 • Slave sensor for electronic differential pressure

45052-EN-131011

Enter the percentage value and the corresponding pressure value for

the max. level.

The quick setup for level measurement is finished.
4. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
5. Min. adjustment

In this menu item you carry out the min. adjustment for flow.
Enter the percentage value and the corresponding pressure value for

the min. flow.
6. Max. adjustment

In this menu item you carry out the max. adjustment for flow.
Enter the percentage value and the corresponding pressure value for

the max. flow.
7. Linearization

In this menu item, you select the characterics of the output signal.

The quick setup for flow measurement is finished.
4. Unit, static pressure

In this menu item, you determine the unit of the static, i.e. superim-

posed pressure.
5. Position correction

In this menu item you compensate the influence of the installation

position of the instrument (offset) to the measured value.
6. zero adjustment

In this menu item you carry out the zero adjustment for the differential

pressure.
Enter the respective pressure value for 0 %.
7. span adjustment

In this menu item you carry out the span adjustment for the differential

pressure
Enter the respective pressure value for 100 %.

Quick setup - Flow meas-

urement

Quick setup - Differential

pressure measurement