6 Set up with the display and adjustment module

VEGAFLEX 83 • Profibus PA

44223-EN-130910

False signal suppression

High sockets and internal vessel installations cause interfering reflec-

tions and can influence the measurement.
A false signal suppression detects, marks and saves these false

signals so that they are no longer taken into account for the level and

interface measurement. We generally recommend carrying out a false

signal suppression to achieve the best possible accuracy. This should

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and

stored.
The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.

AI FB1 Channel

In this menu item you can select the function of the first Function

Block. AI stands for Analog Input.
With this you can adjust the value for the Primary Value (PV). Further

settings (SV, TV) must be carried out via PACTware.

6.4 Parameter adjustment - Extended adjustment

For technically demanding measurement loops you can carry out

extended settings in "Extended adjustment".

The main menu is divided into five sections with the following func-

tions:

Setup: Settings, e.g. measurement loop name, medium, application,

vessel, adjustment, AI FB 1 Channel - Scaling - Damping, device

units, false signal suppression, linearization
Display: Language setting, settings for the measured value indication

as well as lighting
Diagnosis: Information, for example on the instrument status, pointer,

reliability, AI FB 1 simulation, echo curve

Main menu