21

5 Connecting to power supply

VEGAFLEX 83 • Profibus PA

44223-EN-130910

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

The voltage supply is provided by a Profibus DP /PA segment coupler.

The voltage supply range can differ depending on the instrument

version. You can find the data for voltage supply in chapter "Technical

data".

Connection is made with screened cable according to the Profibus

specification. Power supply and digital bus signal are carried over the

same two-wire connection cable.
Use cable with round cross-section. A cable outer diameter of

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

If you are using cable with a different diameter or cross-section,

exchange the seal or use a suitable cable gland.
Please make sure that your installation is carried out according to the

Profibus specification. In particular, make sure that the termination of

the bus is done with appropriate terminating resistors.
You can find detailed information of the cable specification, installa-

tion and topology in the "Profibus PA - User and Installation Guide-

line" on www.profibus.com.

With plastic housing, the NPT cable gland or the Conduit steel tube

must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data".

Make sure that the cable screen and grounding are carried out ac-

cording to Fieldbus specification. We recommend to connect the

cable screen to ground potential on both ends.
With systems with potential equalisation, connect the cable screen

directly to ground potential at the power supply unit, in the connection

box and at the sensor. The screen in the sensor must be connected

directly to the internal ground terminal. The ground terminal outside

on the housing must be connected to the potential equalisation (low

impedance).

5.2 Connecting

The voltage supply and signal output are connected via the spring-

loaded terminals in the housing.
The connection to the display and adjustment module or to the inter-

face adapter is carried out via contact pins in the housing.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and

grounding

Connection technology