VEGA VEGAFLEX 86 Foundation Fieldbus Coax probe User Manual
Page 68
68
11 Supplement
VEGAFLEX 86 • Foundation Fieldbus
44230-EN-130910
Fig. 39: Measuring ranges - VEGAFLEX 86
1 Reference plane
2 Probe length L
3 Measuring range (default setting refers to the measuring range in water)
4 Upper dead band (see diagrams under Accuracy - grey section)
5 Lower dead band (see diagrams under Accuracy - grey section)
Output variable
Output
Ʋ Signal
digital output signal, Foundation Fieldbus protocol
Ʋ Physical layer
according to IEC 61158-2
Damping (63 % of the input variable)
0 … 999 s, adjustable
Channel Numbers
Ʋ Channel 1
Process value
Ʋ Channel 8
Electronics temperature
Ʋ Channel 9
Count rate
Transmission rate
31.25 Kbit/s
Current value
Ʋ Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
Ʋ Ex-d instruments
16 mA, ±0.5 mA
Resolution, digital
> 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
+860 … +1060 mbar/+86 … +106 kPa
(+12.5 … +15.4 psig)
Installation reference conditions
Ʋ Min. distance to installations
> 500 mm (19.69 in)
Ʋ Vessel
metallic, ø 1 m (3.281 ft), centric installation, process
fitting flush with the vessel ceiling
Ʋ Medium
Water/Oil (dielectric constant ~2.0)
1)
Ʋ Installation
Probe end does not touch the vessel bottom
Sensor parameter adjustment
No gating out of false signals carried out
Typical deviation - Interface measure-
ment
± 5 mm (0.197 in)
Typical deviation - Total level interface
measurement
See following diagrams
Typical deviation - Level measurement
2)3)
See following diagrams
1)
With interface measurement = 2.0
2)
Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of
the adjustment or a change of the measured value offset in the DTM service mode
3)
The dead bands can be optimizes by a false signal suppression.