6 Set up with the display and adjustment module
VEGAFLEX 86 • Foundation Fieldbus
44230-EN-130910
Menu item
Default value
Modified value
Max. adjustment - Level
Distance: 0.000 m(d) - note block-
ing distances
Min. adjustment - Level
0 %
Min. adjustment - Level
Distance: Probe length - take dead
band into account
Accept adjustment of the level measurement?
Yes
Max. adjustment - Interface
100 %
Max. adjustment - Interface
Distance: 0.000 m(d) - note block-
ing distances
Min. adjustment - Interface
0 %
Min. adjustment - Interface
Distance: Probe length - take dead
band into account
Integration time - Level
0.0 s
Integration time - Interface
0.0 s
Linearization type
Linear
Linearization - Socket correction
0 mm
Linearization - Vessel height
Probe length
Display
Menu item
Default value
Modified value
Language
Order-specific
Displayed value 1
Filling height Level
Displayed value 2
Electronics temperature
Backlight
Switched off
Diagnostics
Menu item
Default value
Modified value
Status signals - Function control
Switched on
Status signals - Out of specification
Switched off
Status signals - Maintenance
Switched off
Device memory - Echo curve memory
Stopped
Device memory - Measured value memory
Started
Device memory - Measured value memory -
Measured values
Distance level, percentage value
level, reliability level, electronics
temperature
Device memory - Measured value memory - Re-
cording in time interval
3 min.
Device memory - Measured value memory - Re-
cording with measured value difference
15 %
Device memory - Measured value memory - Start
with measured value
Not active