beautypg.com

6 exchanging the cable/rod – VEGA VEGAFLEX 81 4 … 20 mA_HART two-wire User Manual

Page 75

background image

75

9 Diagnostics and service

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

41824-EN-130612

9.6 Exchanging the cable/rod

If necessary, the cable or rod (measuring part) of the probe can be

exchanged.
Loosen the rod or cable with a fork wrench, wrench size 7 (rod ø 8,

cable ø 2 and 4) or wrench size 10 (rod ø 12).
1. Loosen the rod or cable with a fork wrench applied to the flat

surface, provide counterforce with another fork wrench.

2. Unscrew the loosened rod or cable manually.
3. Insert the new measuring rod carefully by hand with a twisting

motion into the opening of the process fitting.

4. Continue screwing in the rod manually into the opening of the pro-

cess fitting.

5. Exert counterforce with the second fork spanner and tighten the

rod or cable on the flat surfaces with the following torque.
Rod ø 8, cable ø 2 and 4: 6 Nm (4.43 lbf ft)
Rod ø 12: 10 Nm (7.37 lbf ft)

Fig. 45: Exchange cable or rod

Information:

Please keep the stated torque so that the max. tensile strength

remains.
6. Enter new probe length and if necessary the new probe type and

then carry out a fresh adjustment (see "Setup procedure, Carry-

ing out min. adjustment - Carrying out max. adjustment").

Exchanging the cable/rod