6 Set up with the display and adjustment module
VEGAFLEX 81 • 4 … 20 mA/HART two-wire
41824-EN-130612
Menu item
Default value
Modified value
Current output - Max.
20.5 mA
Current output 2 - Output variable
Second HART variable (SV)
Distance - Level
Current output 2 - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output 2 - Reaction in case of failure
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Third HART variable (TV)
Measurement certainty, level
Fourth HART variable (QV)
Electronics temperature
Display
Menu item
Default value
Modified value
Language
Order-specific
Displayed value 1
Filling height Level
Displayed value 2
Electronics temperature
Backlight
Switched off
Diagnostics
Menu item
Default value
Modified value
Status signals - Function control
Switched on
Status signals - Out of specification
Switched off
Status signals - Maintenance
Switched off
Device memory - Echo curve memory
Stopped
Device memory - Measured value memory
Started
Device memory - Measured value memory -
Measured values
Distance level, percentage value
level, reliability level, electronics
temperature
Device memory - Measured value memory - Re-
cording in time interval
3 min.
Device memory - Measured value memory - Re-
cording with measured value difference
15 %
Device memory - Measured value memory - Start
with measured value
Not active
Device memory - Measured value memory - Stop
with measured value
Not active
Device memory - Measured value memory - Stop
recording when memory is full
Not active