4 Mounting

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

41824-EN-130612

1

2

3

Fig. 12: Position of the spacer or centering weight
1 Rod probe with spacer (PEEK)

2 Cable probe with centering weight

3 Spacer (PEEK) on the gravity weight of a cable probe

Note:

Measurement in a standpipe is not recommended for extremely

adhesive products.
Instructions for the measurement:

The 100 % point should not be above the upper tube connection

to the vessel

The 0 % point should not be below the lower tube connection to

the vessel

A false signal suppression with installed sensor is generally rec-

ommended to achieve maximum possible accuracy.

If there is a risk of the cable probe touching the vessel wall during

operation due to product movements or agitators, etc., the measuring

probe should be securely fixed.
In the gravity weight there is an internal thread (M8), e.g. for an eye-

bolt (optional) - (article no. 2.1512).
Make sure that the probe cable is not completely taut. Avoid tensile

loads on the cable.
Avoid undefined vessel connections, i.e. the connection must be

either grounded reliably or isolated reliably. Any undefined change of

this requirement can lead to measurement errors.

Fasten