6 Set up with the display and adjustment module

FIBERTRAC 31 • Profibus PA

43833-EN-131119

Make sure that you have selected the correct characteristics. See

menu item "Setup/Current output mode".

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual

"Display and adjustment module".
Display

With this parameter you can change the display language.

This parameter is described in the operating instructions manual

"Display and adjustment module".

With this parameter you can change the indication of the display.

You can choose for example if the display should show the actual

pulse rate or the electronics temperature.

Diagnostics
In this menu item, you can enquire the status of your sensor. In normal

operation, the sensor displays the message "OK". In case of fault, you

will find the corresponding fault code here.
This parameter is described in the operating instructions manual

"Display and adjustment module".

The peak value function holds the max. and min. values during opera-

tion.
This parameter is described in the operating instructions manual

"Display and adjustment module".

Here, you can retrieve the adjustment value of the sensor. This is the

percentage value of the max. pulse rate at which the sensor switches

over.
If you have carried out a single point adjustment, this is the entered

value. With a two-point adjustment, this is the calculated value.
The value is an indication for the reliability and reproducibility of the

switching point.
The greater the difference in the pulse rate between covered and

uncovered status, the greater the differential value (Delta I) and the

more reliable the measurement. The automatically calculated damp-

Lock setup - adjustment

Display - Language

Display - Displayed value

Diagnostics - Device

status

Diagnosis - Peak value

Diagnosis - Adjustment

data