beautypg.com

VEGA POINTRAC 31 Profibus PA User Manual

Page 52

background image

52

11 Supplement

POINTRAC 31 • Profibus PA

43835-EN-131119

AI FB2 (OUT)

– Out value of the AI FB2 after scaling

AI FB3 (OUT)

– Out value of the AI FB3 after scaling

Free Place

– This module must be used if a value in the data telegram of the cyclical data traffic should not

be used (e.g. replacement of temperature and Additional Cyclic Value)

A maximum of three modules can be active. By means of the configuration software of the Profibus

master you can determine the configuration of the cyclical data telegram with these modules. The

procedure depends on the respective configuration software.

Note:

The modules are available in two versions:

Short for Profibus master supporting only one "Identifier Format" byte, e.g. Allen

Bradley

Long for Profibus master only supporting the "Identifier Format" byte, e.g. Siemens

S7-300/400

Examples of telegram configuration

In the following you will see how the modules can be combined and how the appendant data tel-

egram is structured.
Example 1

AI FB1 (OUT)

AI FB2 (OUT)

AI FB3 (OUT)

Byte-

No.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

For-

mat

IEEE-754-Floating point

value

Sta-

tus

IEEE-754-Floating point

value

Sta-

tus

IEEE-754-Floating point

value

Sta-

tus

Value

AI FB1 (OUT)

AI

FB1

AI FB2 (OUT)

AI

FB2

AI FB3 (OUT)

AI

FB3

Example 2

AI FB1 (OUT)

Free Place

Free Place

Byte-No.

1

2

3

4

5

Format

IEEE-754-Floating point value

Status

Value

AI FB1 (OUT)

AI FB1

Note:

Bytes 6-15 are not used in this example.

Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0

Status

Value (IEEE-754)

Fig. 20: Data format of the output signal