9 Diagnosis, asset management and service

VEGABAR 83 • Profibus PA

45037-EN-131107

Code
Text mes-

sage

Cause

Rectification

F013
no measured

value avail-

able

– No valid measured value

available

– Gauge pressure or low

pressure, measuring cell

defective

F017
Adjustment

span too small

– Adjustment not within

specification

– Change the adjustment

according to the limit values

F025
Error in the

linearization

table

– Index markers are not con-

tinuously rising, for example

illogical value pairs

– Check linearization table

– Delete table/Create new

F036
no operable

sensor soft-

ware

– Failed or interrupted soft-

ware update

– Repeat software update

– Check electronics version

– Exchanging the electronics

– Send instrument for repair

F040
Error in the

electronics

– Hardware defect

– Exchanging the electronics

– Send instrument for repair

F041
Error in the

electronics

– No connection to the sensor

electronics

– Check connection to the

sensor electronics (with

detachable version)

F080

– General software error

– Disconnect operating volt-

age briefly

F113
Communi-

cation error,

display and

adjustment

module
Adjustment

software

PACTware out

of order

– EMC interference

– Remove EMC influences

F125
Impermissi-

ble electronics

temperature

– Temperature of the elec-

tronics in the non-specified

section

– Check ambient temperature

– Isolate electronics

– Use instrument with higher

temperature range

F260
Error in the

calibration

– Error in the calibration car-

ried out in the factory

– Error in the EEPROM

– Exchanging the electronics

– Send instrument for repair

F261
Error in the

configuration

– Error during setup

– Error when carrying out a

reset

– Repeat setup

– Repeat reset