10 Supplement

VEGABAR 81 • Modbus and Levelmaster protocol

46293-EN-131107

PV, SV, TV and QV can be adjusted via the sensor DTM.

Register Name

Register Number

Type

Note

Status

100

DWord

Bit 0: Invalid Measurement Value PV
Bit 1: Invalid Measurement Value SV
Bit 2: Invalid Measurement Value TV
Bit 3: Invalid Measurement Value QV

PV Unit

104

DWord

Unit Code

PV

106

Primary Variable in Byte Order CDAB

SV Unit

108

DWord

Unit Code

SV

110

Secondary Variable in Byte Order CDAB

TV Unit

112

DWord

Unit Code

TV

114

Third Variable in Byte Order CDAB

QV Unit

116

DWord

Unit Code

QV

118

Quarternary Variable in Byte Order CDAB

Status

1300

DWord

See Register 100

PV

1302

Primary Variable in Byte Order of Register 3000

SV

1304

Secondary Variable in Byte Order of Register 3000

TV

1306

Third Variable in Byte Order of Register 3000

QV

1308

Quarternary Variable in Byte Order of Register 3000

Status

1400

DWord

See Register 100

PV

1402

Primary Variable in Byte Order CDAB

Status

1412

DWord

See Register 100

SV

1414

Secondary Variable in Byte Order CDAB

Status

1424

DWord

See Register 100

TV

1426

Third Variable in Byte Order CDAB

Status

1436

DWord

See Register 100

QV

1438

Quarternary Variable in Byte Order CDAB

Status

2000

DWord

See Register 100

PV

2002

DWord

Primary Variable in Byte Order ABCD (Big Endian)

SV

2004

DWord

Secondary Variable in Byte Order ABCD (Big Endian)

TV

2006

DWord

Third Variable in Byte Order ABCD (Big Endian)

QV

2008

DWord

Quarternary Variable in Byte Order ABCD (Big En-

dian)

Status

2100

DWord

See Register 100

PV

2102

DWord

Primary Variable in Byte Order DCBA (Little Endian)