11 Supplement
VEGAPULS 66 enamel • Modbus and Levelmaster protocol
41368-EN-121011
11.4 FC4 Read Input Register
With this command, any number (1-127) of input registers can be read out. The start register, from
which the readout should start, and the number of registers are transmitted.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
N*2 Bytes
1 to 127 (0x7D)
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
2*N
Register Value
N*2 Bytes
Data
11.4 FC6 Write Single Register
With this function code an individual holding register can be written.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x06
Start Address
2 Bytes
0x0000 to 0xFFFF
Number of Registers
2 Bytes
Data
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x04
Start Address
2 Bytes
2*N
Register Value
2 Bytes
Data
11.4 FC8 Diagnostics
With this function code different diagnostic functions can be triggered or diagnostic values read out.
Request:
Parameter
Length
Code/Data
Function Code
1 Byte
0x08
Sub Function Code
2 Bytes
Data
N*2 Bytes
Data
Response:
Parameter
Length
Code/Data
Function Code
1 Byte
0x08
Sub Function Code
2 Bytes
Data
N*2 Bytes
Data