11 Supplement

VEGAPULS 66 enamel • Modbus and Levelmaster protocol

41368-EN-121011

1,0 m (3.28 ft)

20 mm (0.788 in)

- 20 mm (- 0.788 in)

0

8 mm (0.315 in)

- 8 mm (- 0.315 in)

1

2

3

Fig. 45: Deviation under reference conditions
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Reproducibility

≤ ±1 mm

Variables influencing measurement accuracy
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm

Additional deviation through strong, high

frequency electromagnetic fields acc. to

EN 61326

< ±50 mm

Influence of the superimposed gas and pressure to the accuracy
The propagation speed of the radar impulses in gas or vapour above the medium is reduced by

high pressure. This effect depends on the superimposed gas or vapour and is especially large at

low temperatures.
The following table shows the resulting deviation for some typical gases and vapours. The specified

values refer to the distance. Positive values mean that the measured distance is too large, negative

values that the measured distance is too small.

Gas phase

Temperature

Pressure

1 bar

(14.5 psig)

10 bar

(145 psig)

50 bar

(725 psig)

100 bar

(1450 psig)

200 bar

(2900 psig)

Air

20 °C/68 °F

0.00 %

0.22 %

1.2 %

2.4 %

4.9 %

200 °C/392 °F -0.01 %

0.13 %

0.74 %

1.5 %

3.0 %

400 °C/752 °F -0.02 %

0.08 %

0.52 %

1.1 %

2.1 %

Hydrogen

20 °C/68 °F

-0.01 %

0.10 %

0.61 %

1.2 %

2.5 %

200 °C/392 °F -0.02 %

0.05 %

0.37 %

0.76 %

1.6 %

400 °C/752 °F -0.02 %

0.03 %

0.25 %

0.53 %

1.1 %

Steam (satu-

rated steam)

100 °C/212 °F 0.26 %

-

-

-

-

180 °C/356 °F 0.17 %

2.1 %

-

-

-

264 °C/507 °F 0.12 %

1.44 %

9.2 %

-

-

366 °C/691 °F 0.07 %

1.01 %

5.7 %

13.2 %

76.0 %