10 Supplement
VEGABAR 83 • Modbus and Levelmaster protocol
46295-EN-131107
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
Ʋ Percentage value
-10 … 110 %
Ʋ Pressure value
-20 … 120 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
Ʋ zero
-20 … +95 %
Ʋ span
-120 … +120 %
4)
Ʋ Difference between zero and span
max. 120 % of the nominal range
Recommended max. turn down
20 : 1 (no limitation)
Nominal measuring ranges and overload capability in bar/kPa
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-
terial and version of the process fitting are possible. The specifications on the nameplate apply.
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +0.1 bar/0 … +10 kPa
+15 bar/+1500 kPa
-1 bar/-100 kPa
0 … +0.4 bar/0 … +40 kPa
+30 bar/+3000 kPa
-1 bar/-100 kPa
0 … +1 bar/0 … +100 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
0 … +2.5 bar/0 … +250 kPa
+50 bar/+5000 kPa
-1 bar/-100 kPa
0 … +10 bar/0 … +1000 kPa
+90 bar/+9000 kPa
-1 bar/-100 kPa
0 … +25 bar/0 … +2500 kPa
+130 bar/+13000 kPa
-1 bar/-100 kPa
-1 … 0 bar/-100 … 0 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
-1 … +1.5 bar/-100 … +150 kPa
+40 bar/+4000 kPa
-1 bar/-100 kPa
-1 … +10 bar/-100 … +1000 kPa
+90 bar/+9000 kPa
-1 bar/-100 kPa
-1 … +25 bar/-100 … +2500 kPa
+130 bar/+13000 kPa
-1 bar/-100 kPa
-0.05 … +0.05 bar/-5 … +5 kPa
+15 bar/+1500 kPa
-0.2 bar/-20 kPa
-0.2 … +0.2 bar/-20 … +20 kPa
+20 bar/+2000 kPa
-0.4 bar/-40 kPa
-0.5 … +0.5 bar/-50 … +50 kPa
+35 bar/+3500 kPa
-1 bar/-100 kPa
Absolute pressure
0 … 0.1 bar/0 … 10 kPa
15 bar/1500 kPa
0 bar abs.
0 … 0.4 bar/0 … 40 kPa
30 bar/3000 kPa
0 bar abs.
0 … 1 bar/0 … 100 kPa
35 bar/3500 kPa
0 bar abs.
0 … 2.5 bar/0 … 250 kPa
50 bar/5000 kPa
0 bar abs.
0 … 10 bar/0 … 1000 kPa
90 bar/9000 kPa
0 bar abs.
0 … 25 bar/0 … 2500 kPa
130 bar/13000 kPa
0 bar abs.
Nominal measuring ranges and overload capacity in psi
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-
terial and version of the process fitting are possible. The specifications on the nameplate apply.
4)
Values less than -1 bar cannot be set.