7 Set up with the display and adjustment module
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
With the function "Proof test", the function of the instrument can be
checked on a recurring basis.
During the function test, the safety function must be treated as unsafe.
Keep in mind that the function test influences downstream connected
devices.
You can find detailed information on the proof test in the Safety
Manual (SIL).
Entering a 4-digit PIN protects the sensor data against unauthorized
access and unintentional modification. In this menu item, the PIN is
displayed or edited and changed. However, this menu item is only
available if adjustment is enabled in the menu "Lock/Release setup/
adjustment".
In delivery status, the PIN is "0000".
In this menu item, the internal clock of the sensor is adjusted.
With a reset, certain parameter adjustments carried out by the user
are reset.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
ment from the factory incl. the order-specific settings. A created false
Diagnosis - Proof test
Additional settings - PIN
Additional adjustments -
Date Time
Additional adjustments
- Reset