Quick start – VEGA VEGAFLEX 82 4 … 20 mA_HART two-wire Rod and cable probe With SIL qualification User Manual
Page 2
2
Quick start
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
Quick start
The quick start procedure enables a quick setup with many applica-
tions. You can find further information in the respective chapters of the
operating instructions manual.
1. Distance from the metallic vessel wall > 300 mm. Distance from
non-metallic vessel wall > 500 mm. The probe must not touch any
installations or the vessel wall.
2. In non-metallic vessels, place a metal sheet beneath the process
fitting.
1
2
Fig. 1: Installation in plastic silo
1 Flange
2 Metal sheet
3. If necessary, fasten probe end.
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-
tions on the type label.
2. Connect the instrument according to the following illustration
5
1
2
+
( )
(-)
6 7 8
4...20mA
2
3
4
1
Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 For external display and adjustment unit
4 Ground terminal for connection of the cable screen
See also chapter "Connecting to power supply"
1. In this menu item you can select the application.
Mounting
Electrical connection
Set parameters