VEGA VEGAFLEX 82 4 … 20 mA_HART two-wire Rod and cable probe With SIL qualification User Manual
Page 3
3
Quick start
VEGAFLEX 82 • 4 … 20 mA/HART two-wire
44222-EN-130823
2. In the menu item "Medium - Dielectric constant" you can define
the medium type (medium).
3. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
4. A "Linearization" is recommended for all vessels in which the
vessel volume does not increase linearly with the level - e.g. in a
horizontal cylindrical or spherical tank. Activate the appropriate
curve.
The sensor measures the distance from the sensor (reference plane)
to the product surface.
4
5
3
1
2
4
1
2
3
5
Fig. 3: Measuring ranges - VEGAFLEX 82
1 Reference plane
2 Probe length L
3 Measuring range
4 Upper dead band (in this area no measurement is possible)
5 Lower dead band (in this area no measurement is possible)
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
other distances, for example, 10 % and 90 % is also possible. Starting
point for these distance specifications is always the seal surface of
the thread or flange.
1. In the menu "Additional settings", menu item "Damping" you can
adjust the requested damping of the output signal.
2. Select the parameter of the current output and the output charac-
teristics in the menu item "Current output".
Parameterization example
Further steps