beautypg.com

VEGA VEGAFLEX 81 4 … 20 mA_HART - four-wire User Manual

Page 32

background image

32

6 Set up with the display and adjustment module

VEGAFLEX 81 • 4 … 20 mA/HART - four-wire

41825-EN-130314

reference plane (seal surface of the process fitting). Keep in mind that

the max. level must lie below the dead band.
Min. adjustment

In this menu item, you can enter the min. adjustment for the level.
Enter the suitable distance value in m for the empty vessel (e.g.

distance from the flange to the probe end) corresponding to the per-

centage value. The distance refers tot he sensor reference plane (seal

surface of the process fitting).

Max. adjustment - Interface

Carry out the max. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value

in m for the full vessel.
Min. adjustment - Interface

Carry out the min. adjustment for the interface.
To do this, enter the percentage value and the suitable distance value

in m for the empty vessel.

Linearization

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank, when the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
The linearization applies for the measured value indication and the

current output. By activating the suitable curve, the percentage vessel

volume is displayed correctly.
False signal suppression

High sockets and internal vessel installations cause interfering reflec-

tions and can influence the measurement.
A false signal suppression detects, marks and saves these false

signals so that they are no longer taken into account for the level and

interface measurement. We generally recommend carrying out a false

signal suppression to achieve the best possible accuracy. This should

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and

stored.

Linearization