beautypg.com

3 combination master - slave – VEGA VEGABAR 81 Save sensor - Operating Instructions User Manual

Page 14

background image

14

4 Mounting

VEGABAR 81 • Slave sensor for electronic differential pressure

45049-EN-131011

The process assembly of instruments with Second Line of Defense

(gastight leadthrough) is completely encapsulated. An absolute pres-

sure measuring cell is used so that no ventilation is required.

1

1

Fig. 7: Position of the filter element - gastight leadthrough
1 Filter element

With relative pressure measuring ranges, the ambient pressure is

detected and compensated by a reference sensor in the electronics.

The filter element is mounted into the electronics housing. It has the

following functions:

Ventilation electronics housing

Atmospheric pressure compensation (with relative pressure meas-

uring ranges)

1

Fig. 8: Position of the filter element - IP 69K version
1 Filter element

Instruments with absolute pressure have a blind plug mounted

instead of the filter element.

4.3 Combination Master - Slave

In principle, any sensor combination within the VEGABAR 80 series is

allowed. The following requirements must be fulfilled:

Configuration, Master sensor suitable for electronic differential

pressure

Pressure type is identical for both sensors, i.e. relative pressure/

relative pressure or absolute pressure/absolute pressure

The master sensor must always measure the higher pressure

Measurement setup as shown in the following chapters

Instruments in IP 69K

version