beautypg.com

VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire User Manual

Page 49

background image

49

6 Set up with the display and adjustment module

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

41844-EN-130612

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Note:

A false signal suppression detects, marks and saves these false

signals so that they are no longer taken into account for the level and

interface measurement. We generally recommend carrying out a false

signal suppression to achieve the best possible accuracy. This should

be done with the lowest possible level so that all potential interfering

reflections can be detected.
Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and

stored.
Note:

Check the distance to the product surface, because if an incorrect

(too large) value is entered, the existing level will be saved as a false

echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

The instrument carries out an automatic false signal suppression

as soon as the probe is uncovered. The false signal suppression is

always updated.
The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.

In the menu item "Lock/unlock adjustment", you can protect the

sensor parameters against unauthorized modification. The PIN is

activated/deactivated permanently.
The following adjustment functions are possible without entering the

PIN:

Setup - False signal sup-

pression

Lock/release setup - Ad-

justment