VEGA VEGAFLEX 86 4 … 20 mA_HART two-wire User Manual
Page 48
48
6 Set up with the display and adjustment module
VEGAFLEX 86 • 4 … 20 mA/HART two-wire
41844-EN-130612
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
If a supplementary electronics with a second current output is im-
plemented in the instrument, then you can adjust the second current
output separately.
In menu item"Current output 2" you specify which measured value
the second current output refers to.
The procedure corresponds to the previous settings of the standard
current output. See "Setup - Current output".
Since the HART variables are very extensive, the indication was
divided into two menu items.
In the menu "HART variables 1" you can have the first HART value PV
(primary value) and the second HART value SV (secondary value) of
the sensor displayed.
The values cannot be changed in the display and adjustment module.
To change these values, you have to use the adjustment software
PACTware.
In the menu "HART variables 2" you can have the third HART value
TV (third value) and the fourth HART value QV (quarter value) of the
sensor displayed.
The values cannot be changed in the display and adjustment module.
To change these values, you have to use the adjustment software
PACTware.
Setup - Current output
Min./Max.
Setup - Current output 2
Setup - HART variables
(1)
Setup - HART variables
(2)