6 Set up with the display and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - four-wire
41835-EN-130314
be displayed in percent but e.g. in l or kg, a scaling can be also set in
the menu item "Display".
Caution:
Note the following, if the respective sensor is used as part of an over-
fill protection system according to WHG:
If a linearization curve is selected, the measuring signal is no longer
linearly proportional to the level. This must be taken into consideration
by the user, particularly when setting the switching point on the limit
signal indicator.
Since the scaling is very comprehensive, the scaling of the level value
was divided into two menu items.
In menu item "Level 1" you define the scaling size and the scaling unit
for the level value on the display, e.g. volume in l.
In menu item "Level 2" you define the scaling format on the display
and the scaling of the level measured value for 0 % and 100 %.
Since scaling is very extensive, the scaling of the interface value was
divided into two menu items.
In menu item "Interface 1" you define the scaling size and the scaling
unit for the interface value on the display, e.g. volume in l.
Setup - Scaling Level
Setup - Scaling Level 1
Setup - Scaling Level 2
Setup - Scaling Interface
Setup - Scaling Interface