VEGA VEGAFLEX 83 4 … 20 mA_HART - four-wire PFA insulated User Manual
Page 28
28
6 Set up with the display and adjustment module
VEGAFLEX 83 • 4 … 20 mA/HART - four-wire
41835-EN-130314
– Save value
•
[->] key:
– Presentation change measured value
– Select list entry
– Select editing position
•
[+] key:
– Change value of the parameter
•
[ESC] key:
– interrupt input
– Jump to next higher menu
The sensor is adjusted via the four keys of the display and adjust-
ment module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration.
Approx. 10 minutes after the last pressing of a key, an automatic reset
to measured value indication is triggered. Any values not confirmed
with [OK] will not be saved.
After switching on, the VEGAFLEX 83 carries out a short self-test
where the device software is checked.
The output signal transmits a fault signal during the switch-on phase.
The following information is displayed on the display and adjustment
module during the startup procedure:
•
Instrument type
•
Device name
•
Software version (SW-Ver)
•
Hardware version (HW-Ver)
With the [->] key you can move between three different indication
modes.
In the first view, the selected measured value and a respective bar-
graph presentation are displayed.
In the second view, the selected measured value as well as a second
selectable value, e.g. the temperature value are displayed.
In the third view, the selected measured value is displayed in large
letters.
6.3 Parameter adjustment - Quick setup
To quickly and easily adapt the sensor to the application, select
the menu item "Quick setup" in the start graphic on the display and
adjustment module.
Adjustment system
Switch-on phase
Measured value indica-
tion
Quick setup