background image

20

4 Mounting

VEGAFLEX 83 • 4 … 20 mA/HART - four-wire

41835-EN-130314

Fig. 11: Mounting of the sensor with inflowing medium

The reference plane for the measuring range of the sensors is the

sealing surface of the thread or flange.
Keep in mind that a min. distance must be maintained below the refer-

ence plane and possibly also at the end of the probe - measurement

in these areas is not possible (dead band). The length of the cable

can be used all the way to the end only when measuring conductive

products. These blocking distances for different mediums are listed

in chapter "Technical data". Keep in mind for the adjustment that the

default setting for the measuring range refers to water.

The process fitting must be sealed if there is gauge or low pressure in

the vessel. Before use, check if the seal material is resistant against

the measured product and the process temperature.
The max. permissible pressure is specified in chapter "Technical

data" or on the type label of the sensor.

To compensate the normal bias voltage loss due to the seal materials,

you have to use also disc springs in addition to the flange screws for

fastening PTFE plated flanges.
The flange screws of VEGAFLEX 83 must always be tightened with

a torque of approx. 60 Nm (44 lbf ft) so that the PTFE washer seals

reliably.

Measuring range

Pressure

Torque with PTFE plated

flanges