7 Maintenance and fault rectification

VEGASWING 66 • - two-wire

43758-EN-130322

Error

Cause

Rectification

VEGASWING 66

signals "covered"

without being sub-

merged (overflow

protection)
VEGASWING 66

signals "uncov-

ered" when being

submerged (dry

run protection)

Operating voltage

too low

Check operating voltage

Electronics de-

fective

Press the mode switch on the signal

conditioning instrument. If the instru-

ment then changes the mode, the

vibrating element may be covered with

buildup or mechanically damaged.

Should the switching function in the

correct mode still be faulty, return the

instrument for repair.
Press the mode switch on the signal

conditioning instrument. If the instru-

ment then does not change the mode,

the electronics module is defective.

Exchange the electronics module.

Unfavourable in-

stallation location

Mount the instrument at a location in

the vessel where no dead zones or air

bubbles can form.

Buildup on the vi-

brating element

Check the vibrating element and

the sensor if there is buildup and re-

move it.

Wrong mode se-

lected

Set the correct mode on the signal

conditioning instrument (overflow pro-

tection, dry run protection). Wiring

should be carried out according to the

quiescent current principle.

Red control lamp

lights

Error on the vi-

brating element

Check if the vibrating element is dam-

aged or extremely corroded.

Interference on

the electronics

module

Exchanging the electronics module

instrument de-

fective

Exchange the instrument or send it in

for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

7.3 Exchanging the electronics

If the electronics module is defective, it can be replaced by the user.
In Ex applications only an electronics module with respective Ex ap-

proval may be used.
You find all information to the electronics exchange in the operating

instructions of the new electronics module.
In general, all electronics modules of series SG60HT can be inter-

changed. If you want to use an electronics module with a different

signal output, you must carry out the complete setup. You can find

the necessary, corresponding operating instructions manual on our

homepage.

Checking the switching

signal

Reaction after fault recti-

fication