Mapping of process value status – VEGA FIBERTRAC 31 Foundation Fieldbus User Manual
Page 70
70
11 Supplement
FIBERTRAC 31 • Foundation Fieldbus
41780-EN-131119
FF descriptor
Rel. In-
dex
Description
Unit
POINT_LEVEL_AD-
JUST_MODE
54
Point level adjustment mode
-
RELAY_VALUE_SEL
55
Relay basic value
-
DIGITAL_IN
56
Frequency of digital input
-
DIGITAL_IN_BOOL
57
State of digital input
-
ANALOG_IN
58
Current on analog input
-
FF_CHANNEL_AVAIL-
ABLE
59
Available channels
-
FF_CHANNEL_USED
60
Used channels
-
Mapping of Process Value Status
Hex
Quality
Sub-Status
Condition
0x00
Bad
Non-specific
Unexpected error
0x01
Bad
Configuration Error
It was tried to set a wrong unit with FF interface
On user error codes: 16, 17, 25, 52, 57, 66, 72,
117, 120
0x0C
Bad
Device Failure
Five or more internal communications have failed
while "Process Data Update". Last usable value is
displayed
On user error codes: 8, 34, 35, 36, 37, 38, 73, 80,
86, 121, 122, 141
0x10
Bad
Sensor Failure
On user error codes: 40, 41, 53, 68, 123, 124, 125
0x1C
Bad
Out of Service
Transducer block is in mode "Out of Service"
Channel is not assigned to an AIFB
Channel is not available in running application
0x20
Bad
Transducer in MAN
Transducer block is in mode "Manual"
0x44
Uncertain
Last Usable Value
Three or more internal communications have failed
while "Process Data Update". Last usable value is
displayed
0x48
Uncertain
Substitute
On user error codes: 29
0x4C
Uncertain
Initial Value
After startup of device or channel assignment in
AIFB was changed. The channel unit may be un-
known until next "Process Data Update"
On user error codes: 13
0x80
Good (NC)
Non-specific
No errors concerning to channel handling
On user error codes: 0, 33, 45, 71, 126, 127
Mapping of User Error Codes to FF Field Diagnostics
Priority
Description
User Error Codes
NE-107 Status
31
Hardware failure
40, 41
FAILURE
30
Memory failure
34, 35, 36, 37
FAILURE