beautypg.com

VEGA FIBERTRAC 31 Foundation Fieldbus User Manual

Page 15

background image

15

4 Mounting

FIBERTRAC 31 • Foundation Fieldbus

41780-EN-131119

Mount the FIBERTRAC 31 in such a way that the detector tube is

directly in the radiated area of the source container. Mount the FIBER-

TRAC 31 preferably side by side and make sure that no detector tube

is hidden by another sensor.

On vessels with temperature insulation, the sensor and the source

container should be preferably mounted outside of the tank insulation.

Fig. 5: Level measurement on a heated vessel with heat insulation

If this is not possible, make sure that there is a sufficiently large

cut-out in the tank insulation for mounting the sensor and the source

container. Make sure that the max. ambient temperature of the sensor

is not exceeded.

If the max. ambient temperature is exceeded, you must take suitable

measures to protect the instrument against overheating.
You can protect the instrument by providing a suitable insulation

against the heat or mounting the instrument further away from the

heat source.
Make sure these measures are taken into account already in the plan-

ning stage. If you want to carry out such measures later on, contact

our specialists to ensure that the accuracy of the application is not

impaired.
If these measures are not sufficient to maintain the max. ambient

temperature, you could consider using the water cooling system we

offer for FIBERTRAC 31.

Vessel with heat insula-

tion

Protection against heat