VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual
Page 48
l
Basic settings: Resetting of the parameter settings incl. special
and laboratory parameters to the default values of the respective
instrument. Any created false signal suppression, user program-
mable linearization curve, measured value memory as well as
event memory will be deleted.
l
Setup: Resetting of the parameter settings to the default values of
the respective instrument . Order-related settings remain but are
not taken over into the current parameters. User-generated false
signal suppression, user-programmed linearization curve, meas-
ured value memory, echo curve memory as well as event memory
remain untouched. The linearization is set to linear.
l
False signal suppression: Deleting a previously created false
signal suppression. The false signal suppression created in the
factory remains active.
l
Peak values measured value: Resetting of the measured min.
and max. distances to the actual measured value.
Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 62:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Bulk solids/Crushed stones, gravel
Application
Storage tank
Silo
Vessel form
Vessel bottom, dished boiler end
Vessel top, dished boiler end
Vesell height/
Measuring range
Recommended measuring range, see
"
Technical data
"
in the supplement
Min. adjustment
Recommended measuring range, see
"
Technical data
"
in the supplement
Max. adjustment
0,000 m(d)
AI FB
1 Channnel PV (lin. perc.)
AI FB
1 scaling
unit
Height
%
AI FB
1 scaling
0.00 lin %, 0.00 %
100.00 lin %, 100.00 %
AI FB
1 damping
0 s
Lock operation
Released
Display
Language
Like order
Displayed value
SV
1
48
VEGAPULS
62 • Approval according to LPR radio standard
6 Set up with the indicating and adjustment module
41720
-EN
-120301