VEGA VEGABAR 86 4 … 20 mA_HART - Operating Instructions User Manual

Page 66

background image

66

11 Supplement

VEGABAR 86 • 4 … 20 mA/HART

45039-EN-131010

Non-compensated temperature range

-40 … 0 °C (-40 … +32 °F), -100 … +130 °C

(+212 … +276 °F)

Nominal measuring range in bar/

kPa

Nominal measuring

range in psig

In the compensated

temperature range

In the non-compen-

sated temperature

range

0 … 10 bar/0 … 1000 kPa

0 … 150 psig

< {0.05 % + 0.1 x

(0.5+0.5 x TD)}

< {0.1 % + 0.15 x

(0.5+0.5 x TD)}

0 … 25 bar/0 … 2500 kPa

0 … 350 psig

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< {0.1 % + 0.2 x

(0.5+0.5 x TD)}

< {0.1 % + 0.3 x

(0.5+0.5 x TD)}

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< {0.15 % + 0.4 x

(0.5+0.5 x TD)}

< {0.15 % + 0.6 x

(0.5+0.5 x TD)}

Thermal change, current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

The thermal change of the current output corresponds to the value F

a

in chapter "Calculation of the

total deviation (according to DIN 16086)".

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 38: Thermal change, current output

>>>Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to the

analogue current output 4 … 20 mA under reference conditions. The specifications refer to the set

span. Turn down (TD) is the ratio nominal measuring range/set span.
The long-term drift of the zero signal corresponds to the value F

Stab

in chapter "Calculation of the

total deviation (according to DIN 16086)".
Long-term drift of the zero signal

Time period

All measuring ranges

Measuring range

0 … +0.025 bar/0 … +2.5 kPa

One year

< 0.05 % x TD

< 0.1 % x TD

Five years

< 0.1 % x TD

< 0.2 % x TD

Ten years

< 0.2 % x TD

< 0.4 % x TD