9 Supplement

VEGABAR 82 • Slave sensor for electronic differential pressure

45050-EN-131011

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 5 psi

435 psi

0 psi

0 … 15 psi

510 psi

0 psi

0 … 30 psi

725 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 300 psi

1900 psi

0 psi

0 … 900 psi

2900 psi

0 psi

0 … +1450 psig
(only for measuring cell ø 28 mm)

2900 psig

0 psi

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+15 … +25 °C (+59 … +77 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation (according to IEC 60770)
Specifications refer to the set span. Turn down (TD) is the ratio: nominal measuring range/set span.

Accuracy class

Non-linearity, hysteresis and re-

peatability with TD 1 : 1 up to 5 : 1

Non-linearity, hysteresis and re-

peatability with 5 : 1

0.05 %

< 0.05 %

< 0.01 % x TD

0.1 %

< 0.1 %

< 0.02 % x TD

0.2 %

< 0.2 %

< 0.04 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span
Turn down (TD) is the relation nominal measuring range/adjusted span.
Measuring cell - Standard

Medium or ambient tem-

perature T

Accuracy class 0.05 %,

0.1 %

Accuracy class 0.2 %

Accuracy class 0.2 %

with measuring range

0.1 bar

abs

-40 … 0 °C (-40 … +32 °F) < {0.15 % + 0.015 %/K x (-

T)} x {0.5+0.5 x TD}

< {0.1 % + 0.03 %/K x (-T)}

x {0.5+0.5 x TD}

< {0.30 % + 0.03 %/K x (-

T)} x {0.5+0.5 x TD}

0 … 40 °C

(+32 … +104 °F)

< {0.0075 %/K x (T -

20 °C)} x {0.5+0.5 x TD}

< {0.005 %/K x (T - 20 °C)}

x {0.5+0.5 x TD}

< {0.015 %/K x (T - 20 °C)}

x {0.5+0.5 x TD}

40 … 100 °C

(+104 … +212 °F)

< {0.15 % } x {0.5+0.5 x

TD}

< {0.005 %/K x (T - 20 °C)}

x {0.5+0.5 x TD}

< {0.3 % } x {0.5+0.5 x TD}