6 Set up with the display and adjustment module
VEGABAR 82 • Slave sensor for electronic differential pressure
45050-EN-131011
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Min. adjustment" and confirm
with [OK].
2. Edit the mbar value with [OK] and set the cursor to the requested
position with [->].
3. Set the requested mbar value with [+] and store with [OK].
4. Change with [ESC] and [->] to the span adjustment
The min. adjustment is finished.
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Proceed as follows:
1. Select with [->] the menu item "Max. adjustment" and confirm
with [OK].
2. Edit the mbar value with [OK] and set the cursor to the requested
position with [->].
3. Set the requested mbar value with [+] and store with [OK].
The max. adjustment is finished.
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "zero adjustment" and confirm
with [OK].
2. Edit the mbar value with [OK] and set the cursor to the requested
position with [->].
3. Set the requested mbar value with [+] and store with [OK].
4. Change with [ESC] and [->] to the span adjustment
The zero adjustment is finished.
Information:
The zero adjustment shifts the value of the span adjustment. The
span, i.e. the difference between these values, however, remains
unchanged.
Setup - Max. adjustment,
flow
Setup - zero adjustment,
differential pressure