6 Set up with the display and adjustment module

VEGABAR 82 • Slave sensor for electronic differential pressure

45050-EN-131011

The following applications are available:

Level

Flow

Differential pressure

Density

Interface

Note:

It is absolutely necessary to activate the slave sensor in advance to

have the applications displayed in the electronic differential pressure

measurement menus.

Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

In this menu item, you determine the units for the "Min. adjustment/

zero" and "Max. adjustment/span" as well as the static pressure.

If the level should be adjusted in a height unit, the density of the me-

dium must also be entered later during the adjustment.
In addition, the unit for the measuring cell and electronics temperature

is determined in the menu item "Peak values".
Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

Particularly with chemical seal systems, the installation position of

the instrument can shift the measured value (offset). The position

correction compensates this offset. Hence the actual measured value

is accepted automatically. With relative pressure measuring cells also

a manual offset can be carried out. With a master/slave combination,

the position correction is carried out for both sensors.

If the actual measured value should be taken over as correction value

during automatic position correction, this value must not be influ-

enced by product coverage or static pressure.
With the manual position correction, the offset value can be deter-

mined by the user. Select for this purpose the function "Edit" and

enter the requested value.

Setup - Units

Setup - Position correc-

tion