beautypg.com

Cyclical data traffic, Module of the pa sensors, Free place – VEGA VEGABAR 66 Profibus PA - climate compensated User Manual

Page 62

background image

62

10 Supplement

VEGABAR 66 • Profibus PA - climate compensated

36792-EN-130321

66 you have to use the general GSD file PA139701.GSD. If the general GSD file is used, the sensor

must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-

ates with the manufacturer-specific ID number.

Note:

When using the profile-specific GSD file, the PA-OUT value as well as the temperature

value are transmitted to the PLC (see block diagram "Cyclical data traffic").

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-

tion. The below block diagram below shows which data can be accessed by the PLC.

bar

%

Lin%

Min-Max

adjustment

Linearization

PROFIBUS PA-output

Primary

Value

Secondary

Value 1

Secondary

Value 2

Target

Mode

Failure

mode

Alarms

Scaling

Source for

scaling

t

i

Damping

Sensor

characteristics

PA-Out

TB

FB

Select additional cyclic

value

Sensor mounting

correction

Fig. 33: VEGABAR 66: Block diagram with AI (PA-OUT) value and Additional Cyclic Value

PROFIBUS PA-output

Target

Mode

Failure

mode

Alarms

Scaling

Source for

scaling

t

i

Damping

Sensor

characteristics

PA-Out

°C

TB

FB 2

Fig. 34: VEGABAR 66: Block diagram with temperature value

Module of the PA sensors

For the cyclic data traffic, VEGABAR 66 provides the following modules:

AI (PA-OUT)

– PA-OUT value of the FB1 after scaling

Temperature

– PA-OUT value of the FB2 after scaling

Additional Cyclic Value

– Additional cyclical value (depending on the source)

Free Place