10 Supplement
VEGABAR 66 • Profibus PA - climate compensated
36792-EN-130321
Nominal measuring range
in bar/kPa
Nominal measuring
range in psig
Average temperature co-
efficient of the zero signal
and the output span, in
the compensated temper-
ature range 0 … +100 °C
(+32 … +212 °F), refer-
ence temperature 20 °C
(68 °F)
Average temperature co-
efficient of the zero signal
and the output span, out-
side the compensated
temperature range
0 … 150 psig
< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%
0 … 25 bar/0 … 2500 kPa
0 … 350 psig
< (0.05 + 0.1 x TD)% < (0.1 + 0.15 x TD)%
Thermal change of the current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output
< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C
(-40 … +176 °F)
0,15 %
-0,15 %
-40°C
-20°C
20°C
40°C
60°C
80°C
Fig. 32: Thermal change, current output
Long-term stability (according to DIN 16086 and IEC 60770-1)
Applies to digital HART interface as well as to analogue current output 4 … 20 mA. Specifications
refer to the set span. Turn down (TD) is the relation nominal measuring range/set span.
Nominal measuring range in bar/kPa
Nominal measuring
range in psig
Long-term drift of the zero signal
0 … 0.2 bar/0 … 20 kPa
0 … 3 psig
< (1 % x TD)/year
0 … 0.4 bar/0 … 40 kPa
0 … 6 psig
< (1 % x TD)/year
0 … 1 bar/0 … 100 kPa
0 … 15 psig
< (0.25 % x TD)/year
0 … 2.5 bar/0 … 250 kPa
0 … 35 psig
< (0.25 % x TD)/year
0 … 5 bar/0 … 500 kPa
0 … 70 psig
< (0.1 % x TD)/year
0 … 10 bar/0 … 1000 kPa
0 … 150 psig
< (0.1 % x TD)/year
0 … 25 bar/0 … 2500 kPa
0 … 350 psig
< (0.1 % x TD)/year
Ambient conditions
Ambient, storage and transport temperature
Ʋ Version with connection tube
-40 … +80 °C (-40 … +176 °F)
Ʋ Version with suspension cable FEP,
PUR
-20 … +80 °C (-4 … +176 °F)