Input variable
Measured variable

The measured quantity is the distance between process

fitting of the sensor and product surface. The reference

plane is the seal surface on the hexagon or the lower

side of the flange.

3

4

2

1

Fig. 55: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Standard electronics
Max. measuring range

35 m (114.83 ft)

Recommended measuring range

Ʋ Antenna ø 40 mm (1.575 in)

up to 15 m (49.21 ft)

Ʋ Antenna ø 48 mm (1.89 in)

up to 20 m (65.62 ft)

Ʋ Antenna ø 75 mm (2.953 in), ø 95 mm

(3.74 in), parabolic antenna

up to 35 m (114.83 ft)

Electronics with increased sensitivity
Max. measuring range

75 m (246.1 ft)

Recommended measuring range

Ʋ Antenna ø 40 mm (1.575 in)

up to 15 m (49.21 ft)

Ʋ Antenna ø 48 mm (1.89 in)

up to 20 m (65.62 ft)

Ʋ Antenna ø 75 mm (2.953 in)

up to 40 m (131.23 ft)

Ʋ Antenna ø 95 mm (3.74 in)

up to 50 m (164 ft)

Ʋ Parabolic antenna

up to 75 m (246.1 ft)

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Damping (63 % of the input variable)

0 … 999 s, adjustable