beautypg.com

VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire User Manual

Page 25

background image

25

4 Mounting

VEGAPULS 61 • 4 … 20 mA/HART - two-wire

36499-EN-121011

The measurement through a ball valve with complete run is pos-

sible

Constructional requirements on the bypass pipe:

Material metal, smoother inner tube

In case of an extremely rough tube inner surface, use an inserted

tube (tube in tube) or a radar sensor with tube antenna

Flanges are welded to the tube according to the orientation of the

polarisation level

Gap size with junctions ≤ 0.1 mm, for example, when using a ball

valve or intermediate flanges with single pipe sections

The antenna diameter of the sensor should correspond to the

inner diameter of the tube

Diameter should be constant over the complete length

The short examples give you introductory information on the flow

measurement. Detailed planning information is available from flume

manufacturers and in special literature.

h

ma

x

d

mi

n

≥ 2 mm x h

ma

x

90°

4

3 ... 4 h

max

≥ 50 mm

90°

2

3

1

Fig. 22: Flow measurement with rectangular flume: d

min.

= min. distance of the

sensor (see chapter "Technical data"); h

max.

= max. filling of the rectangular

flume
1 Overflow orifice (side view)

2 Headwater

3 Tail water

4 Overfall orifice (view from bottom water)

In general, the following points must be observed:

Install the sensor on the headwater side

Installation in the centre of the flume and vertical to the liquid

surface

Distance to the overfall orifice

Distance of orifice opening above ground

Min. distance of the orifice opening to bottom water

Min. distance of the sensor to max. storage level

Flow measurement with

rectangular flume