11 Supplement
VEGAPULS 65 • Profibus PA
36517-EN-121011
Ambient conditions
Ambient, storage and transport tempera-
ture
-40 … +80 °C (-40 … +176 °F)
Process conditions
For the process conditions, please also note the specifications on the type label. The lower value
always applies.
Process temperature (measured on the process fitting)
Ʋ Process fitting, thread PVDF
-40 … +130 °C (-40 … +266 °F)
Ʋ Other process fittings
-40 … +150 °C (-40 … +302 °F)
Vessel pressure
Ʋ Screwed part PVDF
-1 … 2 bar (-100 … 200 kPa/-14.5 … 29.0 psig)
Ʋ Screwed part and flange 316L
-1 … 16 bar (-100 … 1600 kPa/-14.5 … 232 psig)
Vessel pressure relating to the flange
nominal stage
see supplementary instructions manual "Flanges ac-
cording to DIN-EN-ASME-JIS"
Vibration resistance
4 g at 5 … 200 Hz according to EN60068-2-6 (vibration
with resonance)
Shock resistance
100 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Options of the cable entry
Ʋ Cable gland
M20 x 1.5 (cable: ø 5 … 9 mm)
Ʋ Cable entry
½ NPT
Ʋ Blind stopper
M20 x 1.5; ½ NPT
Ʋ Closing cap
M20 x 1.5; ½ NPT
Plug options
Ʋ Signal circuit
M12 x 1, according to ISO 4400, Harting HAN, 7/8" FF
Ʋ Indication circuit
M12 x 1
Wire cross-section (spring-loaded terminals)
Ʋ Massive wire, cord
0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ Stranded wire with end sleeve
0.2 … 1.5 mm² (AWG 24 … 16)
Electromechanical data - version IP 66/IP 68 (1 bar)
Options of the cable entry
Ʋ Cable gland with integrated connec-
tion cable
M20 x 1.5 (cable: ø 5 … 9 mm)
Ʋ Cable entry
½ NPT
Ʋ Blind stopper
M20 x 1.5; ½ NPT
Connection cable
Ʋ Wire cross-section
0.5 mm² (AWG 20)
Ʋ Wire resistance
< 0.036 Ω/m
Ʋ Tensile strength
< 1200 N (270 lbf)
Ʋ Standard length
5 m (16.4 ft)