VEGA VEGAPULS 65 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual
Page 3
3
Quick start
VEGAPULS 65 • Profibus PA
36517-EN-121011
3. Select in the menu item "Application" the vessel, the application
and the vessel form, for example, storage tank.
4. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
The radar sensor measures the distance from the sensor to the
product surface. For indication of the real level, an allocation of the
measured distance to the percentage height must be carried out.
100%
0%
2
1
1 m
(39.37
")
10 m (393.7
")
Fig. 3: Parameterization example
1 Min. level = max. meas. distance
2 Max. level = min. meas. distance
For this adjustment, the distance is entered with full and virtually
empty vessel. If these values are not known, an adjustment with
distances, for example, of 10 % and 90 % is also possible. Starting
point for these distance specifications is always the seal surface of
the thread or flange.
1. In the menu "Additional settings", menu item "Damping" you have
to adjust the requested damping of the output signal.
2. Select the output characteristics in the menu item "Current out-
put".
The quick start is then finished. For further information see chapter
"Parameter adjustment".
Parameterization example
Further steps