3 Product description

VEGABAR 55 • Profibus PA

36735-EN-130321

This operating instructions manual applies to the following instrument

versions:

Software from 3.82

3.2 Principle of operation

VEGABAR 55 is a pressure transmitter for use in the chemical, food

processing and pharmaceutical industries. Depending on the version,

it is used for level, gauge, absolute pressure or vacuum measure-

ment. Measured products are gases, vapours and liquids, also those

with higher temperatures.

The METEC

®

measuring cell is the measuring unit. It consists of

the ceramic-capacitive CERTEC

®

measuring cell and a special,

temperature-compensated isolating system.
The hydrostatic pressure of the product or the process pressure

causes a capacitance change in the measuring cell via the metallic

process diaphragm and the isolating liquid. This change is converted

into a corresponding output signal.

Power supply via the Profibus DP/PA segment coupler or VEGALOG

571 EP cards. A two-wire cable according to Profibus specification

serves as carrier of both power and digital data transmission for

multiple sensors. The instrument profile of VEGABAR 55 corresponds

to profile specification version 3.0.
The backlight of the display and adjustment module is powered by the

sensor. Prerequisite is a certain level of operating voltage.
The data for power supply are specified in chapter "Technical data".
The optional heating requires its own operating voltage. You can find

details in the supplementary instructions manual "Heating for display

and adjustment module".
This function is generally not available for approved instruments.

The GSD (instrument master files) and bitmap files necessary for

planning your Profibus-DP-(PA) communication network are available

from the download section on the VEGA homepage www.vega.com

under "Services - Downloads - Software - Profibus". There you can

also find the appropriate certificates. In a PDM environment, an EDD

(Electronic Device Description) is also required to enable the full

range of sensor functions (also available as a download).A CD with

the appropriate files can be ordered via e-mail under [email protected].

com or by phone from one of the VEGA agencies under the order

number "DRIVER.S".

3.3 Operation

The instrument can be adjusted with the following adjustment media:

With the display and adjustment module

with the suitable VEGA DTM in conjunction with an adjustment

software according to the FDT/DTM standard, e.g. PACTware and

PC

Scope of this operating

instructions manual

Application area

Functional principle

Power supply and bus

communication

GSD/EDD