beautypg.com

VEGA VEGABAR 55 Profibus PA User Manual

Page 52

background image

52

10 Supplement

VEGABAR 55 • Profibus PA

36735-EN-130321

Ʋ Double chamber housing

– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x

blind plug M20 x 1.5; plug M12 x 1 for the external

display and adjustment unit (optional)

or:

– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT, plug

M12 x 1 for the external display and adjustment unit

(optional)

or:

– 1 x plug (depending on the version), 1 x blind plug

M20 x 1.5; plug M12 x 1 for the external display and

adjustment unit (optional)

or:

– 2 x blind stoppers M20 x 1.5; plug M12 x 1 for the

external display and adjustment unit (optional)

Spring-loaded terminals for wire cross-

section

< 2.5 mm² (AWG 14)

Electromechanical data - version IP 66/IP 68 (1 bar)
Cable entry

Ʋ Single chamber housing

– 1 x IP 68 cable gland M20 x 1.5; 1 x blind plug

M20 x 1.5

or:

– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT

Connection cable

Ʋ Configuration

four wires, one suspension wire, one breather capillary,

screen braiding, metal foil, mantle

Ʋ Wire cross-section

0.5 mm² (AWG 20)

Ʋ Wire resistance

< 0.036 Ω/m (0.011 Ω/ft)

Ʋ Tensile strength

> 1200 N (270 pounds force)

Ʋ Standard length

5 m (16.4 ft)

Ʋ Max. length

1000 m (3281 ft)

Ʋ Min. bending radius at 25 °C/77 °F

25 mm (0.985 in)

Ʋ Diameter approx.

8 mm (0.315 in)

Ʋ Colour - Non-Ex version

Black

Ʋ Colour - Ex-version

Blue

Electromechanical data - version IP 68
Connection cable between IP 68 instrument and external housing:

Ʋ Configuration

four wires, one suspension wire, one breather capillary,

screen braiding, metal foil, mantle

Ʋ Wire cross-section

0.5 mm² (AWG 20)

Ʋ Wire resistance

< 0.036 Ω/m (0.011 Ω/ft)

Ʋ Standard length

5 m (16.40 ft)

Ʋ Max. length

180 m (590.5 ft)

Ʋ Min. bending radius at 25 °C/77 °F

25 mm (0.985 in)