VEGA VEGABAR 55 Profibus PA User Manual
Page 49
49
10 Supplement
VEGABAR 55 • Profibus PA
36735-EN-130321
Nominal range
Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … +70 psig
+700 psig
-15 psig
0 … +150 psig
+700 psig
-15 psig
0 … +350 psig
+700 psig
-15 psig
-15 … 0 psig
+500 psig
-15 psig
-15 … +25 psig
+700 psig
-15 psig
-15 … +70 psig
+700 psig
-15 psig
-15 … +150 psig
+700 psig
-15 psig
-15 … +350 psig
+700 psig
-15 psig
-0.7 … +0.7 psig
+200 psig
-15 psig
-1.5 … +1.5 psig
+290 psig
-15 psig
-3 … +3 psig
+430 psig
-15 psig
-7 … +7 psig
+500 psig
-15 psig
Absolute pressure
0 … 15 psi
500 psi
0 psi
0 … 35 psi
700 psi
0 psi
0 … 70 psi
700 psi
0 psi
0 … 150 psi
700 psi
0 psi
0 … 350 psi
700 psi
0 psi
Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature
18 … 30 °C (64 … 86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)
Determination of characteristics
limit point adjustment according to DIN 16086
Characterstic curve
Linear
Reference installation position
upright, diaphragm points downward
Influence of the installation position
< 5 mbar/0.5 kPa (0.07 psig)
Deviation determined according to the limit point method according to IEC 60770
10)
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation with version 0.075 %
Ʋ Turn down 1 : 1 up to 5 : 1
< 0.075 %
Ʋ Turn down > 5 : 1
< 0.015 % x TD
Deviation with version 0.1 %
Ʋ Turn down 1 : 1 up to 5 : 1
< 0.1 %
10)
Incl. non-linearity, hysteresis and non-repeatability.