beautypg.com

4 exchanging the electronics module, 5 software update – VEGA VEGABAR 67 Profibus PA User Manual

Page 49

background image

49

8 Maintenance and fault rectification

VEGABAR 67 • Profibus PA

36743-EN-130321

Total deviation digital output signal absolute:

F

total

= 0.35 % x 147 mbar/100 % = 0.46 mbar = 4.7 mm

Basic accuracy analogue output signal in percent:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= 0.05 %/10 K x TD

F

Kl

= 0.1 %

F

a

= 0.15 %

F

perf

= √((0.05 %/10 K x 20 K x 1.4)

2

+ (0.1 %)

2

+ (0.15 %)

2

)

F

perf

= 0.23 %

Total deviation analogue output signal in percent:

F

total

= F

perf

+ F

stab

F

stab

= 0.1 %/year x TD

F

stab

= 0.1 %/year x 1.4

F

stab

= 0.14 %

F

total

= 0.23 % + 0.14 % = 0.37 %

Total deviation analogue output signal absolute:

F

total

= 0.37 % x 147 bar/100 % = 0.54 mbar = 5.5 mm

8.4 Exchanging the electronics module

In case of a defect, the electronics module can be exchanged by the

user against an identical type. If no electronics module is available on

side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial

number. The electronics module with serial number includes order-

specific data such as factory setting, seal material etc. These are not

included in the electronics module without serial number.
The serial number is stated on the type label of VEGABAR 67 or on

the delivery note.

8.5 Software update

The software version of VEGABAR 67 can be determined as follows:

on the type label of the electronics

Via the display and adjustment module

via PACTware

You can view all software histories on our website www.vega.com.

Make use of this advantage and get registered for update information

via e-mail.
The following components are required to update the sensor soft-

ware:

Sensor

Voltage supply

VEGACONNECT

PC with PACTware

Current sensor software as file