47
9 Supplement
VEGABAR 55 • 4 … 20 mA
36733-EN-130321
Ʋ For one year
< 0.05 % x TD
Ʋ For five years
< 0.1 % x TD
Ʋ For ten years
< 0.2 % x TD
Ambient conditions
Ambient, storage and transport temperature
Ʋ Standard version
-40 … +80 °C (-40 … +176 °F)
Ʋ Versions IP 66/IP 68 (1 bar) and IP 68
(25 bar), connection cable PUR
-20 … +80 °C (-4 … +176 °F)
Ʋ Version IP 66/IP 68 (1 bar), connec-
tion cable PE
-20 … +60 °C (-4 … +140 °F)
Process conditions
The specifications of the pressure stage and product temperature are used as an overview. The
specifications on the type label are applicable.
Pressure stage, process fitting
Ʋ Thread 316L, depending on connec-
tion
PN 25, PN 60
Ʋ Thread Aluminium
PN 25
Ʋ Hygienic fittings 316L, depending on
connection
PN 6, PN 10, PN 25, PN 40 (PN 40 only with DRD and
DIN 11851)
Ʋ Flange 316L
PN 16/PN 40 or 150 lb/300 lb
Product temperature
Ʋ Standard
-12 … +140 °C (+10 … +284 °F)
Ʋ with extenation, extended thread or
Clamp 2½"
-12 … +140 °C (+10 … +284 °F)
Ʋ with cooling element
-12 … +180 °C (+10 … +356 °F)
Ʋ with cooling element and screening
sheet
-12 … +200 °C (+10 … +392 °F)
Vibration resistance
mechanical vibrations with 4 g and 5 … 100 Hz
9)
Shock resistance
Acceleration 100 g/6 ms
10)
Electromechanical data - version IP 66/IP 67
Cable entry/plug
11)
Ʋ Single chamber housing
– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5
or:
– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
– 1␣x plug (depending on the version), 1␣x blind stopper
M20␣x␣1.5
or:
– 2 x blind plug M20 x 1,5
9)
Tested according to the guidelines of German Lloyd, GL directive 2.
10)
Tested according to EN 60068-2-27.
11)
Depending on the version M12 x 1, according to ISO 4400, Harting, 7/8" FF.