10 Supplement
VEGABAR 54 • Foundation Fieldbus
36732-EN-130321
Ʋ unassembled
IP 20
Ʋ mounted into the sensor without cover IP 40
Material
Ʋ Housing
ABS
Ʋ Inspection window
Polyester foil
Voltage supply
Operating voltage
Ʋ Non-Ex instrument
9 … 32 V DC
Ʋ Ex ia instrument
9 … 24 V DC
Ʋ Ex d instrument
9 … 32 V DC
Operating voltage with illuminated display and adjustment module
Ʋ Non-Ex instrument
12 … 32 V DC
Ʋ Ex-ia instrument
12 … 24 V DC
Ex d instrument
12 … 32 V DC
Power supply by/max. number of sensors
Ʋ H1 power supply
max. 32 (max. 10 with Ex)
Electrical protective measures
Protection rating
Ʋ Housing, standard
IP 66/IP 67
15)
Ʋ Aluminium and stainless housing
(optionally available)
IP 68 (1 bar)
16)
Ʋ Process component in IP 68 version IP 68 (25 bar)
Ʋ External housing
IP 65, IP 66/IP 68 (0.2 bar)
Overvoltage category
III
Protection class
II
Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"
and "serial number search" as well as via "Downloads" and "Approvals".
10.2 Information on Foundation Fieldbus
Block diagram, measured value processing
The following illustration shows the Transducer Block and Function block in simplified form.
15)
Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.
in water. This can lead to falsification of the measured value.
16)
Only with instruments with absolute pressure ranges.