VEGA VEGABAR 54 Foundation Fieldbus User Manual

Page 49

background image

49

10 Supplement

VEGABAR 54 • Foundation Fieldbus

36732-EN-130321

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

-7 … +7 psig

+500 psig

-15 psig

Absolute pressure
0 … 15 psi

500 psi

0 psi

0 … 35 psi

700 psi

0 psi

0 … 70 psi

900 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 350 psi

1900 psi

0 psi

0 … 900 psi

2900 psi

0 psi

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

+15 … +25 °C (+59 … +77 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Determination of characteristics

Limit point adjustment according to IEC 61298-2

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 0.2 mbar/20 Pa (0.003 psig)

Deviation determined according to the limit point method according to IEC 60770

10)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Influence of the product or ambient temperature
Average temperature coefficient of the zero signal
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
In the compensated temperature range 0 … +100 °C (+32 … +212 °F), reference temperature

20 °C (68 °F).
Average temperature coefficient zero signal

Ʋ Turn down 1 : 1

< 0.05 %/10 K

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %/10 K

10)

Incl. non-linearity, hysteresis and non-repeatability.