VEGA VEGABAR 54 Foundation Fieldbus User Manual
Page 28
28
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 54 • Foundation Fieldbus
36732-EN-130321
Density
0001000
kg/dm³
6. Enter the requested density value with [->] and [+], confirm with
[OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:
4)
1. Activate the selection with [OK] and select "Temperature unit
with [->].
2. Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
3. Confirm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Offset
P
=
+0000 mbar
53 mbar
2. Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
▶
Accept
Edit
3. Confirm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1. Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
+000.0 %
=
+0000.0 mbar
0000.0 mbar
2. Set the requested percentage value with [+] and [->].
3. Confirm with [OK] and edit the requested mbar value.
4. Set the requested mbar value with [+] and [->].
5. Confirm with [+] and move to max. adjustment with [->].
The min. adjustment is finished.
Information:
For an adjustment with filling, simply enter the actual measured value
indicated at the bottom of the display.
Carry out a position cor-
rection
Carry out min. adjustment
4)
Selection options: °C, °F.