VEGA FIBERTRAC 31 4 … 20 mA_HART - four-wire User Manual
Page 52
52
6 Set up with the display and adjustment module
FIBERTRAC 31 • 4 … 20 mA/HART - four-wire
40446-EN-131119
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Isotope
Cs-137
Application
Limit level
Adjustment mode Single point adjustment
Adjustment - un-
covered
90000 ct/s
Adjustment - cov-
ered
9000 ct/s
only with two-point adjustment
Delta I
90 %
Background ra-
diation
0 ct/s
Temperature unit °C
Damping
Is calculated automatically by the in-
strument
Current output
mode
8/16 mA, < 3.6 mA
X-ray alarm
Modulated measuring current
Mode - Relay
Overfill protection
Block adjustment Released
Display
Language
Selected language
Displayed value
Pulse rate
Additional adjust-
ments
Temperature unit °C
HART mode
Standard
With this function you can select the mode.
The sensor offers the HART modes standard and multidrop.
If the measured value is outputted via the 4 … 20 mA output, you
must not switch over to HART Multidrop.
The mode 'Standard', with fixed address 0 (factory setting), means
output of the measured value as 8/16 mA signal.
This parameter is described in the operating instructions manual
"Display and adjustment module".
With this function
•
Load parameter adjustment data from the sensor into the display
and adjustment module
•
Write parameter adjustment data from the display and adjustment
module into the sensor
This parameter is described in the operating instructions manual
"Display and adjustment module".
Info
In this menu you will find the following menu items:
Additional adjustments -
HART mode
Additional adjustments -
Copy instrument settings
Info