6 Set up with the display and adjustment module
FIBERTRAC 31 • 4 … 20 mA/HART - four-wire
40446-EN-131119
Default settings: Resetting of the parameter adjustment like under
"Basic adjustment". In addition, special parameters will be reset to
default values. Order-specific settings will not be deleted.
Peak values measured value: Resetting of the parameter adjust-
ments in the menu item "Setup" to the default values of the respective
instrument. Order-specific settings remain but are not taken over into
the current parameters.
Peak values temperature: Resetting of the measured min. and max.
temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "Level". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Setup
Measurement loop name
Sensor
Isotope
Cs-137
Application
Level
Adjustment
0 %, 100 %
Linearisation
0 ct/s ≙ 100 %
90000 ct/s ≙ 0 %
Background radiation
0 ct/s
Unit of the process value
%
Temperature unit
° C
Damping
60 s (manually)
Real value correction
0
Current output mode
4 … 20 mA, < 3.6 mA
Current output Min./Max.
Min. current 3.8 mA, max. current 20.5 mA
X-ray alarm
Modulated measuring current
Reference value - Relay
None
Mode
Overfill protection
Upper switching point -
Process value
0 %
Lower switching point -
Process value
0 %
Upper switching point -
Temperature
50 °C
Upper switching point -
Temperature
25 °C
Block adjustment
Released
Address - Summation
Slave
free